Thorlux is closed for the Christmas break and will re-open on Thursday 2nd January 2025. Merry Christmas!
Multi-bed Wards
Treatment spaces include a variety of room types ranging from specific treatment for individuals, to group rooms and multi-bed wards (some facilities will have individual bedrooms which are covered separately in this guide). Rooms need to be secure and safe, whilst potentially including a toilet, a waiting area, office/bedroom with en-suite. Therapy rooms can be for relaxation, music, drama or similar so consultation with staff is key to achieving the correct design.
Illumination Levels
Application | Minimum maintained mean illuminance (lux) | Illuminance uniformity (minimum/average) | Notes |
---|---|---|---|
Acute mental health facility | 300 | 0.60 | The lighting should be designed according to the activity, most areas will be staffed constantly. |
Psychiatric intensive care units (PICUs) | 50-300 | 0.60 | Robust anti-ligature fittings required with manual switches operated by the staff. Levels to be provided by dimming or switching. |
High dependency rehabilitation units (HDRUs) | 50-300 | 0.60 | HDRUs can be categorised as low, medium or high risk. See chapter text to determine the specific lighting requirements. |
Child and adult mental health services (CAMHS) | 5-300 | 0.60 | Designer to be mindful that patients could be children or young adults. Different levels required in different areas. Comfortable, low glare, homely but robust schemes are required. |
Dementia assessment areas | 50-300 | 0.60 | Only very low-glare fittings should be used, and luminaires should not be installed in a regular pattern. Design should include for discrete but robust luminaires to give a calming homely feel. |
Places of safety | 5-300 | 0.60 | These spaces are designed to provide a safe and secure environment. |
Night lighting | 5 |